Fiber strands — modelling & rendering (design)

Status: research / design proposal. Nothing here is built yet. This document works out how Danbyte should model, colour, label, and eventually trace the individual fibres inside a fibre cable — a capability NetBox does not have, so it's a genuine differentiator.


1. Why

A fibre cable is not one wire — it's a bundle of strands (2, 12, 24, 48, 96, 144, 288 …). Each strand is a separate light path that can be spliced, patched, labelled, and traced independently. Real fibre plant management lives at the strand level: "trunk T-14, strand 7 (red), goes from panel A rear-3 to panel B rear-9."

NetBox (and Danbyte today) models a cable as a single link with an A end and a B end. There is no notion of how many fibres are inside, no strand colours, no per-strand labels, and no per-strand trace. Adding this makes Danbyte the tool a fibre/OSP team actually wants — and it slots naturally onto the cable + cable type + termination system we already have.

Danbyte already has half of the primitive: a patch-panel RearPort.positions ("Number of strands / front-port positions") with FrontPort.rear_port_position selecting one. So a panel already knows it has N strand positions; what's missing is the same concept on the cable, plus colours, labels, and strand-aware terminations.


2. Fibre colour standard primer (TIA-598-C)

Strand identification in North America (and widely elsewhere) follows TIA-598-C. The other major scheme is IEC 60304 / IEC 60794, which differs mainly in a few hues and in unit ordering — worth allowing as an option, but TIA-598-C is the sensible default.

2.1 The 12-colour base sequence

Positions 1–12 within a unit, in order:

# Colour Hex (suggested) Note
1 Blue #0071CE
2 Orange #FF7A00
3 Green #00A651
4 Brown #7B4A12
5 Slate (grey) #8A8D8F
6 White #F4F4F4 needs a border on light UI
7 Red #E4002B
8 Black #101010 needs a border on dark UI
9 Yellow #FFD100
10 Violet #8246AF
11 Rose (pink) #F4A6C0
12 Aqua #00B5C7

Mnemonic: Blue Orange Green Brown Slate White Red Black Yellow Violet Rose Aqua.

Two of these are traps for a UI: white (#6) disappears on a light surface and black (#8) disappears on a dark surface. The dot renderer must always draw a thin contrasting outline (see §6).

2.2 Beyond 12 fibres — units and tracers

For counts >12 the strands are organised into 12-fibre units (loose-tube "buffer tubes", or 12-fibre "ribbons"). There are two identification methods in the wild, and a cable uses one or the other:

(a) Unit (buffer-tube) colour coding — loose-tube OSP cable. Each 12-fibre tube is itself coloured per the same 12-colour sequence, and the 12 fibres inside each tube run Blue…Aqua again. A strand's identity is the pair (tube colour, fibre colour). Example, 48-fibre (4 tubes):

Tube 1 (Blue):   fibres 1–12  = Blue, Orange, … Aqua
Tube 2 (Orange): fibres 13–24 = Blue, Orange, … Aqua
Tube 3 (Green):  fibres 25–36 = Blue, Orange, … Aqua
Tube 4 (Brown):  fibres 37–48 = Blue, Orange, … Aqua

So strand 25 = "Green tube, Blue fibre."

(b) Ring / tracer marking — ribbon and many tight-buffered cables. The 12 colours repeat, and the repeat group is distinguished by a printed tracer: the second dozen (13–24) carries a mark, the third dozen (25–36) a heavier mark, and so on. Vendors implement the mark as a dash pattern, ring count, or a black tracer stripe.

This is the behaviour you described: the swatch shows the base colour, then gains a black stripe when the count passes 12, and a black ring when the sequence wraps again. That maps cleanly to a single derived value — group = floor((position − 1) / 12) — rendered as escalating marks (§5, §6).

We should model both: store the fibre count, a construction hint (loose-tube / ribbon / tight-buffered), and derive either the (tube, fibre) pair or the ring-count presentation from position.

A duplex optic (LR/SR/…) uses two strands — one TX, one RX. Parallel optics (e.g. 40G-SR4, 100G-SR4 on MPO) use 8 or more. A "link" over a trunk therefore consumes a pair or group of strands, not one. The model should let a termination bind a set of strand positions, not just one, so a duplex LC or an MPO-12 can be represented honestly. (Phase 2 — see §9.)


3. What Danbyte has today (grounding)

  • Cable (api/models.py) — type (from CABLE_TYPE_CHOICES, already includes smf, smf-os1/os2, mmf-om1…om5), color (7-char hex of the jacket), label, status, length, terminations.
  • CableTermination — one endpoint (end A/B) pointing at exactly one of interface / front_port / rear_port / … / power_feed / aux_port. A port is cabled at most once.
  • RearPort.positions — "Number of strands / front-port positions"; FrontPort.rear_port_position selects which strand. So a panel already has a strand axis; the collapse/trace engine (api/cable_points.py, topology_views._collapse, strand_of) already walks front⇄rear by position.
  • Colour renderingColorBadge (frontend/src/components/cells/color-badge.tsx) draws a coloured pill with luminance-picked text; topology port rows draw small KIND_DOT swatches; the tray/trace overlays colour cables by cable.color.

Gap: the cable has no strand count, no per-strand colour/label, and a CableTermination cannot say which strand(s) it lands on. Everything strand-y today lives only on the panel positions axis.


4. Modelling options

Option A — full FiberStrand rows (one row per strand)

class FiberStrand(models.Model):
    cable = FK(Cable, related_name="strands")
    position = PositiveSmallInteger   # 1-based
    label = CharField(blank=True)
    status = CharField(...)           # in-use / spare / damaged / reserved
    # colour is DERIVED from position + standard, never stored
    # (phase 2) a_termination / b_termination FKs for strand-level trace
    unique_together = ("cable", "position")
  • Pros: first-class strand identity, indexable labels, natural home for strand-level terminations (phase 2), per-strand status.
  • Cons: a 288F trunk is 288 rows whether or not anyone annotated them. Violates the repo's "no rows until there's real data" instinct. Heavy to create/copy/delete.

Option B — fiber_count + sparse JSONB on the cable

Cable.fiber_count   = PositiveSmallInteger(null=True)   # only for fibre types
Cable.fiber_standard = CharField(default="tia598c")     # tia598c | iec | custom
Cable.fiber_construction = CharField(default="")        # loose-tube | ribbon | tight
Cable.strands = JSONField(default=dict)  # sparse: {"7": {"label": "...", "status": "damaged"}}

Colours are derived from position + fiber_standard. Labels/status live in a sparse dict keyed by position — no storage until a strand is actually annotated (fits the zero-pre-filled-data ethos, mirrors custom_fields).

  • Pros: cheap, zero rows for un-annotated strands, dead-simple to render, ships fast. Enough for visualisation + labelling (the headline ask).
  • Cons: can't (yet) attach a strand to a specific far-end position — the cable's A/B terminations stay whole-cable.

Start with B (count + sparse JSONB) for Phase 1. When strand-level termination/splice is needed (Phase 2), promote to sparse FiberStrand rows created only for strands that are labelled or terminated — the JSONB labels migrate into rows lazily. Best of both: cheap when idle, relational when it matters.

Recommendation: ship Option B now, design the JSONB shape so it can be migrated into Option A rows later without a rewrite (keep position the key in both).

fiber_count as a real column (not custom_fields) is justified the same way length is: it's an intrinsic structural attribute of the cable, not tenant business data. The colour table is an industry spec (like CABLE_TYPE_CHOICES and LENGTH_UNITS, which we already ship), so shipping TIA-598-C as the default reference is consistent with the codebase — see §8.


5. Colour + marking derivation (single source of truth)

One pure function, shared by backend (for API-provided swatches / exports) and frontend (for rendering). Given a 1-based position, the count, and the standard:

TIA598C = [Blue, Orange, Green, Brown, Slate, White,
           Red, Black, Yellow, Violet, Rose, Aqua]   # {name, hex}

fiberColor(position, standard = "tia598c"):
    palette = PALETTES[standard]              # 12 entries
    idx     = (position - 1) % 12
    group   = (position - 1) // 12            # 0 for 1–12, 1 for 13–24, …
    base    = palette[idx]                    # {name, hex}
    return {
      position,
      name:   base.name,
      hex:    base.hex,
      group,                                  # which dozen (unit / ribbon)
      # presentation marks (the behaviour you described):
      stripe: group >= 1,                     # black tracer stripe once past 12
      rings:  max(0, group - 1),              # +1 black ring each further wrap
      # (loose-tube alt) the containing unit's own colour:
      unit:   palette[group % 12],            # tube colour for (tube,fibre) id
      unitIndex: group,
    }
  • 1–12 → solid colour, no mark.
  • 13–24 → same colours + one black stripe (stripe = true).
  • 25–36+ one black ring (rings = 1), 37–48 → two rings, …
  • For loose-tube construction, also expose unit so the UI can label a strand as "Green tube · Blue fibre" instead of / in addition to the rings.

This is deliberately presentation-agnostic: the function yields facts (group, stripe, rings, unit); the renderer decides marks vs tube-colour based on fiber_construction.


6. Rendering

6.1 <FiberDot> — the atomic swatch

A small round (or squircle) swatch, the fibre analogue of the existing status dots. Props: position, count, standard, size, optional label.

  • Fill = hex.
  • Outline = always a 1px contrasting ring (rgba picked from luminance) so White(#6), Aqua(#12), Yellow(#9) read on light surfaces and Black(#8) reads on dark — reuse readableText()'s luminance logic from ColorBadge.
  • Stripe = a black diagonal bar across the swatch when stripe (13–24).
  • Rings = rings concentric black rings inside the outline (25–36 = 1, …).
  • Tooltip = "T-14 · fibre 25 · Blue · Green tube (unit 3)".

Renders as inline SVG (matches the topology dot convention — no icon lib).

6.2 <FiberMap> — the strip on the cable page

Given fiber_count, draw the strands as a grid grouped into rows of 12 (one row per unit/ribbon), each cell a <FiberDot> with its position number and (if set) its label. A unit's leading swatch can carry the tube colour for loose-tube cables. Interactions:

  • Click a strand → inline label / status editor (writes Cable.strands[pos]).
  • Hover → tooltip; the strand highlights on the trace map (§6.4).
  • Header shows count, standard, construction; a legend chip explains stripe = 2nd dozen, ring = further dozens.

Lives on the cable detail page as a "Fibres" section, and read-only inside the topology/trace deep-view.

6.3 Cable type / interface type integration

  • The Fibres section only appears when type is a fibre medium (smf*, mmf*) — reuse the existing CABLE_TYPE_CHOICES grouping to decide.
  • Interface media/type already exists; a fibre interface implies a strand demand (duplex = 2, MPO-8 = 8). Phase 2 can pre-select that many strands when cabling.

6.4 Topology / trace integration

  • Where a cable edge is drawn today (RoutedEdge, tray overlays), a fibre cable can render as a thin multi-line bus or carry a small count-strand legend; hovering a strand in the <FiberMap> highlights that strand's path through the trace (reusing the existing highlight machinery).
  • The topology port-row dots (stencil-node.tsx) can show the terminating strand colour for a fibre link instead of the generic kind dot.

6.5 Exports

Include the fibre map (colours + labels + tube grouping) in the cable PNG / the floor-plan pull-sheet, so a splicer can work off the printout.


7. Strand labelling

  • Where: Cable.strands[position].label (Option B) — sparse, only stored when set. Free text (e.g. "Cust-A pri", "spare", "dark").
  • Bulk: a "label all" helper (prefix + auto-number), and copy-from-far-end.
  • Status per strand: in-use | spare | reserved | damaged | dark — drives a muted / hatched swatch so a splicer sees dead fibres at a glance.
  • Search/filter: strand labels should be searchable (phase 2 promotes to rows so this is an index, not a JSON scan).

8. Zero-pre-filled-data considerations

  • The TIA-598-C colour sequence is an industry standard, the same category as CABLE_TYPE_CHOICES, LENGTH_UNITS, and the media list we already ship. So shipping it as a built-in reference palette is consistent — it is not tenant business data.
  • Still, honour flexibility: fiber_standard is a choice (tia598c default, iec alternative), and a tenant may define a custom palette in the customization app (a 12-entry colour list) selected as custom. That keeps regional/vendor variance user-controlled without forcing a default on anyone.
  • No strand rows, labels, or counts are created until the user sets them.

9. Phasing

Phase 1 — visualise + label (Option B). Cable.fiber_count, fiber_standard, fiber_construction, strands (JSONB). Shared fiberColor() function. <FiberDot> + <FiberMap>. Cable-page Fibres section with click-to-label + per-strand status. Read-only map in the trace deep-view. Exports include it. — Delivers the headline value.

Phase 2 — strand-level terminations & trace.

Phase 2a — multi-fibre connectors (shipped). FrontPort.positions (+ template) gives a connector a fibre count, so an LC-duplex (2) or MPO (8–24) claims a range of rear positions [start … start+positions−1] — overlap and fit validated in FrontPort.clean(); a connector-type quick-fill (dcim_choices.CONNECTOR_FIBERS) pre-fills it. cable_points.strand_of is range-aware (a rear position resolves to the covering front port + local fibre index). A per-tenant FiberSettings.strand_modelling (off/count/accurate) gates how much fibre UI appears.

Phase 2b — the strand map (next). Add CableTermination.strand_map (sparse {cable strand → port position}, null = straight-through). A connect- time dialog (polarity presets: straight / crossed / custom) writes it, and strand_of follows it when present — so a run tracks the exact strand through duplex/MPO and crossed polarity. Promote heavily-annotated strands to sparse FiberStrand rows if/when label indexing is needed.

Phase 3 — splices & OSP. Splice points (fusion/mechanical) between strands of different trunks, loss budget per strand, buffer-tube management, and fibre routing on the floor-plan tray system (a tray already carries cables — let it carry strand assignments).


10. Open questions (for the user)

  1. Marking convention: default to the stripe-at-13, ring-at-25 scheme you described (ribbon/tracer style), or default to tube-colour pairs for loose-tube and use stripes/rings only for ribbon? (We can store construction and do both — this is just the default when unspecified.)
  2. Strand terminations in Phase 1? Ship visualise+label first (Option B), or go straight to strand-level terminations (heavier, Option A/C now)?
  3. Custom palettes: is TIA-598-C default enough for v1, or is a tenant custom palette needed on day one?
  4. Where the count comes from: manual fiber_count, or inferred from the cable type + a chosen connector (e.g. "24F MPO trunk")?

11. Concrete first slice (if approved)

  1. Migration: add fiber_count (null int), fiber_standard (default tia598c), fiber_construction (blank), strands (JSONB {}) to Cable. Guard in the serializer so they only validate/serialise for fibre types.
  2. api/fiber_colors.py — the palette table + fiber_color(position, standard) (backend twin of the frontend function; keeps API exports honest).
  3. frontend/src/lib/fiber.tsfiberColor() + palettes (single FE source).
  4. frontend/src/components/fiber/FiberDot.tsx, FiberMap.tsx.
  5. Cable detail page: a Fibres section (map + label/status editor), shown only for fibre cable types.
  6. Docs: a user-facing docs/dcim/fiber.md, and a roadmap entry.
  7. Gates: model/serializer tests (colour derivation, sparse strand round-trip, validation that fiber_count is only set for fibre types), tsc, eslint, prettier.